  1. Applications: 

    EZAD-12 is designed to protect triphase AC motors (low voltage – 220/380V) from the whole variety of nominal capacities of electric driven pumps, ventilators, centrifuges, compressors, lifting and transportation mechanisms etc., working in continuous and short-time modes. EZAD-12 is a current protection unit with simplified indication of the normal and malfunction status.

  2. Functions:

    EZAD-12 provides:

    • protection of the electric motor when overloading in a symmetrical mode of power supply;
    • protection of the electric motor in “locked rotor” mode;
    • protection of the electric motor when loss of phase (voltage or current) is occured;
    • protection of the electric motor when there is an inadmissible (over 10%) voltage asymmetry;
    • protection of the electric motor when a bad insulation is occurred(before starting);
    • time-delay of engine startup after powering up.
  3. Technical information and work modes:

     

    • powering voltage : 3x(220 – 240) V/50 Hz;
    • time-delay when a phase is lost – 3 sec.;
    • time-delay if asymmetry is over 10% - 8 sec.;
    • range of time delay: 10 – 300 sec. (if ordered);
    • range of controlled insulation: 1K – 0,5 M; (regulated with trimer – potentiometer);
    • relay output– switching – 8A/220 V AC;
    • protection – IP20 or IP44;
    • current transformer – Ix/5A/5W with external shunt 0,2?/5 W;
    • indicators:


        “swithed on” operating contact “ready” green;
        “malfunction” red
        “overload” blinking red