- Applications:
EZAD-12 is designed to protect triphase AC motors (low voltage – 220/380V) from the whole variety of nominal capacities of electric driven pumps, ventilators, centrifuges, compressors, lifting and transportation mechanisms etc., working in continuous and short-time modes. EZAD-12 is a current protection unit with simplified indication of the normal and malfunction status.
- Functions:
EZAD-12 provides:
- protection of the electric motor when overloading in a symmetrical mode of power supply;
- protection of the electric motor in “locked rotor” mode;
- protection of the electric motor when loss of phase (voltage or current) is occured;
- protection of the electric motor when there is an inadmissible (over 10%) voltage asymmetry;
- protection of the electric motor when a bad insulation is occurred(before starting);
- time-delay of engine startup after powering up.
- Technical information and work modes:
- powering voltage : 3x(220 – 240) V/50 Hz;
- time-delay when a phase is lost – 3 sec.;
- time-delay if asymmetry is over 10% - 8 sec.;
- range of time delay: 10 – 300 sec. (if ordered);
- range of controlled insulation: 1K – 0,5 M; (regulated with trimer – potentiometer);
- relay output– switching – 8A/220 V AC;
- protection – IP20 or IP44;
- current transformer – Ix/5A/5W with external shunt 0,2?/5 W;
- indicators:
“swithed on” operating contact “ready” green; “malfunction” red “overload” blinking red